Add on cooling - INVERTAIR and Fixed speed add on refrigerated matching Braemar TQ extra air ducted gas heaters
- Braemar Invertair's with TQ heaters must use a MagIQtouch controller and be an extra-air heater for additional airflow due to the coil restricting airflow
- Invertair's cannot be used on TG and TH heaters. TG and TH heaters must use fixed speed AOC's with a Spectrolink controller.
- Note: Care must be taken to ensure that the AOC coils Maximum airflow is not exceeded. This can be done by setting the DGH maximum airflow during commissioning and set up stage. Please refer to the TQ DGH installation manual.
- Braemar fixed speed add-on coolers must be used with a MagIQtouch (TQ extra air heaters) Spectrolink (TG & TH extra air heaters) and not a manual t/stat to allow for the 24Vac output to the cooler.
- The AOCF23C-S is specifically designed to be used with a TQA5X30 heater