FP Fault Code – VRF Systems (Outdoor DC Fan Motor Fault)

Applies To

  • Braemar / VRF Systems
  • Outdoor Units (all VRF series using DC fan motors)

Fault Description

The FP fault code is displayed on:

  • Indoor wired controller
  • Indoor display / receiver board
  • Outdoor main PCB

Indicates a fault with the outdoor DC fan motor or associated control circuitry.


Possible Causes

  • Outdoor fan blade obstructed or seized
  • Damaged or burnt-out DC fan motor
  • Fan motor wiring damage / disconnection
  • Poor connection at PCB terminals
  • Faulty outdoor main PCB
  • No motor drive signal from PCB

⚠️ SAFETY WARNING
The outdoor unit contains high voltage components (up to ~350V DC) and moving parts. Failure to follow correct testing procedures may result in electric shock, equipment damage, or personal injury. Ensure safe isolation practices are followed, and only qualified personnel carry out diagnostic checks.


Step-by-Step Troubleshooting

1. Visual Inspection

  • Check outdoor fan operation:
    • Ensure fan rotates freely
    • Remove any debris or obstruction
  • Remove fan blade and:
    • Inspect for damage
    • Spin motor shaft – must rotate smoothly
  • Inspect for motor overheating:
    • Burnt motors may show yellow discoloration

2. Wiring & Connection Checks

  • Inspect fan motor cable for:
    • Cuts, abrasion, or rubbing from fan blade
  • Check all plugs:
    • Fully seated into outdoor PCB
    • No loose or bent pins
  • Inspect PCB terminals for damage

3. Electrical Testing (DC Fan Motor Circuit)

⚠️ Use a multimeter and follow safe electrical practices

Set Multimeter to DC Voltage

TestTerminalsNormal Value
Motor Supply (Vdc)Red ↔ Black232V – 356V DC
Driver Voltage (Vcc)White ↔ Black0 – 15V DC
Speed Signal (Vsp)Yellow ↔ Black2.1V – 6.5V DC
  • Important:
    • Vcc above 15V may damage the PCB


⚠️ Safety Warning: High voltage DC is present. Only qualified technicians should perform testing. Failure to follow safe procedures may result in serious injury or equipment damage.

Set Multimeter to AC Voltage

  • Check incoming supply to outdoor PCB:
    • Normal: 165V – 253V AC

Set Multimeter to Frequency (Hz)

  • Check motor feedback signal:
    • Terminals: Blue ↔ Black
    • Formula:
      Fan Speed (RPM) = Frequency × 5

Diagnosis Guidelines

If ALL values are normal:

  • Vdc, Vcc, Vsp, supply voltage and feedback signal are within range
  • BUT fan does not run or stops:

Conclusion:

  • Internal motor protection likely activated
  • Fan motor is faulty (burnt out) and must be replaced

❌ If Abnormal Readings Found:

ConditionLikely Fault
No Vdc outputFaulty PCB
Vcc out of rangePCB or driver fault
No Vsp signalControl issue (PCB)
No feedback signalMotor failure or wiring fault
No AC supplyPower supply issue

Recommended Actions

  1. Rectify any mechanical obstruction or wiring fault
  2. Repair/replace damaged wiring or connectors
  3. Replace outdoor fan motor if faulty
  4. Replace outdoor PCB if no drive signals present

Important Notes

  • Always isolate power before inspection
  • Only qualified technicians to perform live testing
  • Follow local electrical safety regulations
  • Refer to manufacturer service procedures where required







⚠️ SAFETY WARNING
The outdoor unit contains high voltage components (up to ~350V DC) and moving parts. Failure to follow correct testing procedures may result in electric shock, equipment damage, or personal injury. Ensure safe isolation practices are followed, and only qualified personnel carry out diagnostic checks.