RPSI & EXS Coolers Cutting Out on High Fan Speed LED (A09/24) Due to High Static Pressure – Checking Outlet Capacity


Description

This article explains why RPSI and EXS coolers may cut out on high fan speed when static pressure exceeds design limits and provides guidance on calculating whether existing outlets can deliver the required airflow at 80 Pa.

Issue Summary

  • RPSI/EXS coolers use direct‑drive ECM motors that maintain constant power and adjust fan speed to overcome airflow restrictions.
  • If static pressure is too high (or building pressure is negative), the motor may exceed RPM limits and shut down for safety.
  • Common causes: undersized ductwork, too few or closed outlets, tight bends/long runs, jammed weather seal, or extraction fans creating negative pressure.
  • Target design: ~80 Pa static pressure at the cooler.

Performance Data @ 80 Pa

Model

Airflow @ 80 Pa

RPSI2500

2130 L/s

RPSI2800

2530 L/s

EXS160

1720 L/s

EXS180

2070 L/s

EXS200

2320 L/s

EXS220

2540 L/s

(Sources: ES E257‑A RPSI Technical Data Sheet; ES E081‑G EXS Technical Specifications AU2411)

Outlet Airflow Guide (Typical Domestic Values)

Outlet Size

Typical L/s

300 mm

150–170

350 mm

250–300

400 mm

350–400

450 mm

450–500

500 mm

550–600



Calculation: Is Outlet Capacity ≥ Airflow @80 Pa?

  1. List all outlets and sizes.
Example: 6 × 350 mm + 2 × 400 mm
  1. Multiply by typical L/s per outlet:
    • 6 × 300 L/s = 1800 L/s
    • 2 × 400 L/s = 800 L/s
Total = 2600 L/s
  1. Compare to the cooler airflow @80 Pa:
    • RPSI2500 = 2130 L/s → PASS
    • RPSI2800 = 2530 L/s → PASS
    • EXS200 = 2320 L/s → PASS

PASS Example

  • Outlets: 6 × 350 mm (300 L/s each) + 2 × 400 mm (400 L/s each)
  • Total outlet capacity = (6 × 300) + (2 × 400) = 2600 L/s
  • Cooler airflow @80 Pa = 2530 L/s (RPSI2800)
  • Result: PASS – Outlet capacity exceeds cooler airflow.

FAIL Example

  • Outlets: 4 × 350 mm (300 L/s each)
  • Total outlet capacity = 4 × 300 = 1200 L/s
  • Cooler airflow @80 Pa = 2130 L/s (RPSI2500)
  • Result: FAIL – Outlet capacity is less than cooler airflow. Add outlets or upsize existing ones.

If total outlet airflow < cooler airflow:

  • Add outlets or upsize existing ones.
  • Check duct layout for restrictions (bends, length, diameter).

Quick Reference Table: Outlet Count vs Cooler Airflow

Cooler Model

Airflow @80 Pa

Example Outlet Configurations

Result

RPSI2500

2130 L/s

6 × 350 mm (≈1800 L/s)

FAIL

RPSI2500

2130 L/s

8 × 350 mm (≈2400 L/s)

PASS

RPSI2800

2530 L/s

8 × 350 mm (≈2400 L/s)

Borderline

RPSI2800

2530 L/s

6 × 350 mm + 2 × 400 mm (≈2600 L/s)

PASS

EXS160

1720 L/s

6 × 350 mm (≈1800 L/s)

PASS (outlet performance dependent)

EXS180

2070 L/s

7 × 350 mm (≈2100 L/s)

PASS

EXS200

2320 L/s

8 × 350 mm (≈2400 L/s)

PASS

EXS220

2540 L/s

6 × 350 mm + 2 × 400 mm (≈2600 L/s)

PASS

Use typical outlet airflow values for calculations.) 

Direct‑Drive Motor – Fan Speed LED Diagnostics (RPSI/RPCQi/EXS)

Motor Diagnostic FAN SPEED LED meanings:
  • Solid green = Normal. Fan speed is within the allowed range for the set speed.
  • Flashing green = Over‑speed. Motor is about 20% faster than target; it will shut down in 30 s (sooner at higher speeds). At 30% over target, it stops immediately.
  • Off during a run command = Under‑speed. Motor is about 30% slower than target or hasn’t started; it will shut down after ~30 s at high speed (longer at lower speeds).
Common causes (check these first):
  • High static pressure/restrictions: undersized or squashed duct, tight bends/long runs, too few/closed outlets, short dropper to too few outlets, or weather seal not fully opening.
  • Negative building pressure: big extraction fans or lack of relief openings.
  • Electrical/mechanical: supply voltage out of spec (≤ 207 V or ≥ 253 V), fan installed backwards, worn bearings or internal motor fault.
Why the LED behaves this way (tech note):
  • ECM coolers hold a target input power at each set speed. If airflow is restricted, the controller raises RPM to maintain that power. When RPM goes outside ~±20%, the control enters fault mode, showing over/under‑speed and protecting the motor — which is why restricted systems tend to cut‑out on high speed.
Quick technician checklist:
  1. Confirm total outlet capacity ≥ cooler airflow @80 Pa (see tables above).
  2. Verify the weather seal opens fully; inspect for kinks/squash in duct runs.
  3. Ensure the home has an exhaust/relief path (crack windows/doors if needed).
  4. Check mains voltage is within 230–240 V tolerance.

Preventive Measures

  • Confirm outlet capacity ≥ cooler airflow @80 Pa before installation.
  • Avoid long restrictive runs; ensure registers fully open.
  • Provide adequate exhaust openings to prevent negative pressure.
  • Verify weather seal operation and dropper/transition integrity.

How to Test Static Pressure at the Dropper (Step‑by‑Step)

Important: Measure static pressure with the cooler operating (fan ON) at a steady speed. “Static” refers to the pressure component that acts equally in all directions and is independent of air velocity—it does not mean the system is off.
Goal: Check if the system is operating close to the domestic design target of ~80 Pa. Higher numbers mean restriction; very low numbers can mean too many/open outlets or negative building pressure.

What you need

  • A digital manometer (or U‑tube manometer) that reads in Pascal (Pa).
  • Flexible pressure tube (the small clear hose that plugs into the manometer).
  • 6 mm drill bit and a blanking grommet (or aluminum tape) to seal the hole afterwards.
  • A marker and a bit of tape.

Safety first

  • Turn OFF power to the cooler at the isolation switch.
  • Work from a stable ladder and keep hands clear of moving parts.

Where to make the test hole

  • On a down‑discharge dropper: drill on the side wall just beneath the weather seal, roughly 25–50 mm below the seal lip, on a straight section. This reads the plenum static pressure the cooler “sees”, without extra turbulence.
  • On top/side‑discharge transitions: pick the first straight section before the first bend/branch, ideally 1–2 duct diameters downstream of the outlet.

Step‑by‑step

  1. Drill the hole: Use the 6 mm bit at the location above. Lightly deburr the edges.
  2. Insert the tube: Push the manometer tube through so the tip sits flush with the inner wall (don’t poke it far into the airflow). Seal around the tube with a grommet or tape so air can’t leak.
  3. Power ON and run High Fan: Set the cooler to fan HIGH (ventilation is fine). Make sure the weather seal opens fully. Wait 2–3 minutes for airflow to settle.
  4. Read the pressure: Note the Pa value on the manometer. 
    • Around 80 PaGood for domestic systems.
    • >100 PaRestriction likely (undersized/squashed duct, tight bends, too few/closed outlets, damper not opening).
    • <50 PaToo much outlet area or negative pressure in the house (strong extraction fans, closed windows/doors).
  5. Finish up: Turn power OFF, remove the tube, and seal the hole with a blanking grommet (preferred) or aluminum tape.

Quick tips for a clean reading

  • Keep the tube tip flush and perpendicular to the airflow—this avoids picking up velocity pressure.
  • Don’t measure right next to elbows, take‑offs, dampers, or mesh.
  • Check all outlets are open and the home has a relief path (windows/doors cracked open) so the cooler isn’t fighting negative pressure.
  • If the reading hunts up and down, take a short 5–10 second average (many digital manometers have a damping setting).