RPSI & EXS Coolers Cutting Out on High Fan Speed LED (A09/24) Due to High Static Pressure – Checking Outlet Capacity
Description
Issue Summary
- RPSI/EXS coolers use direct‑drive ECM motors that maintain constant power and adjust fan speed to overcome airflow restrictions.
- If static pressure is too high (or building pressure is negative), the motor may exceed RPM limits and shut down for safety.
- Common causes: undersized ductwork, too few or closed outlets, tight bends/long runs, jammed weather seal, or extraction fans creating negative pressure.
- Target design: ~80 Pa static pressure at the cooler.
Performance Data @ 80 Pa
Model | Airflow @ 80 Pa |
RPSI2500 | 2130 L/s |
RPSI2800 | 2530 L/s |
EXS160 | 1720 L/s |
EXS180 | 2070 L/s |
EXS200 | 2320 L/s |
EXS220 | 2540 L/s |
Outlet Airflow Guide (Typical Domestic Values)
Outlet Size | Typical L/s |
300 mm | 150–170 |
350 mm | 250–300 |
400 mm | 350–400 |
450 mm | 450–500 |
500 mm | 550–600 |
Calculation: Is Outlet Capacity ≥ Airflow @80 Pa?
- List all outlets and sizes.
- Multiply by typical L/s per outlet:
- 6 × 300 L/s = 1800 L/s
- 2 × 400 L/s = 800 L/s
- Compare to the cooler airflow @80 Pa:
- RPSI2500 = 2130 L/s → PASS
- RPSI2800 = 2530 L/s → PASS
- EXS200 = 2320 L/s → PASS
PASS Example
- Outlets: 6 × 350 mm (300 L/s each) + 2 × 400 mm (400 L/s each)
- Total outlet capacity = (6 × 300) + (2 × 400) = 2600 L/s
- Cooler airflow @80 Pa = 2530 L/s (RPSI2800)
- Result: PASS – Outlet capacity exceeds cooler airflow.
FAIL Example
- Outlets: 4 × 350 mm (300 L/s each)
- Total outlet capacity = 4 × 300 = 1200 L/s
- Cooler airflow @80 Pa = 2130 L/s (RPSI2500)
- Result: FAIL – Outlet capacity is less than cooler airflow. Add outlets or upsize existing ones.
If total outlet airflow < cooler airflow:
- Add outlets or upsize existing ones.
- Check duct layout for restrictions (bends, length, diameter).
Quick Reference Table: Outlet Count vs Cooler Airflow
Cooler Model | Airflow @80 Pa | Example Outlet Configurations | Result |
RPSI2500 | 2130 L/s | 6 × 350 mm (≈1800 L/s) | FAIL |
RPSI2500 | 2130 L/s | 8 × 350 mm (≈2400 L/s) | PASS |
RPSI2800 | 2530 L/s | 8 × 350 mm (≈2400 L/s) | Borderline |
RPSI2800 | 2530 L/s | 6 × 350 mm + 2 × 400 mm (≈2600 L/s) | PASS |
EXS160 | 1720 L/s | 6 × 350 mm (≈1800 L/s) | PASS (outlet performance dependent) |
EXS180 | 2070 L/s | 7 × 350 mm (≈2100 L/s) | PASS |
EXS200 | 2320 L/s | 8 × 350 mm (≈2400 L/s) | PASS |
EXS220 | 2540 L/s | 6 × 350 mm + 2 × 400 mm (≈2600 L/s) | PASS |
Direct‑Drive Motor – Fan Speed LED Diagnostics (RPSI/RPCQi/EXS)
- Solid green = Normal. Fan speed is within the allowed range for the set speed.
- Flashing green = Over‑speed. Motor is about 20% faster than target; it will shut down in 30 s (sooner at higher speeds). At 30% over target, it stops immediately.
- Off during a run command = Under‑speed. Motor is about 30% slower than target or hasn’t started; it will shut down after ~30 s at high speed (longer at lower speeds).
- High static pressure/restrictions: undersized or squashed duct, tight bends/long runs, too few/closed outlets, short dropper to too few outlets, or weather seal not fully opening.
- Negative building pressure: big extraction fans or lack of relief openings.
- Electrical/mechanical: supply voltage out of spec (≤ 207 V or ≥ 253 V), fan installed backwards, worn bearings or internal motor fault.
- ECM coolers hold a target input power at each set speed. If airflow is restricted, the controller raises RPM to maintain that power. When RPM goes outside ~±20%, the control enters fault mode, showing over/under‑speed and protecting the motor — which is why restricted systems tend to cut‑out on high speed.
- Confirm total outlet capacity ≥ cooler airflow @80 Pa (see tables above).
- Verify the weather seal opens fully; inspect for kinks/squash in duct runs.
- Ensure the home has an exhaust/relief path (crack windows/doors if needed).
- Check mains voltage is within 230–240 V tolerance.
Preventive Measures
- Confirm outlet capacity ≥ cooler airflow @80 Pa before installation.
- Avoid long restrictive runs; ensure registers fully open.
- Provide adequate exhaust openings to prevent negative pressure.
- Verify weather seal operation and dropper/transition integrity.
How to Test Static Pressure at the Dropper (Step‑by‑Step)
What you need
- A digital manometer (or U‑tube manometer) that reads in Pascal (Pa).
- Flexible pressure tube (the small clear hose that plugs into the manometer).
- 6 mm drill bit and a blanking grommet (or aluminum tape) to seal the hole afterwards.
- A marker and a bit of tape.
Safety first
- Turn OFF power to the cooler at the isolation switch.
- Work from a stable ladder and keep hands clear of moving parts.
Where to make the test hole
- On a down‑discharge dropper: drill on the side wall just beneath the weather seal, roughly 25–50 mm below the seal lip, on a straight section. This reads the plenum static pressure the cooler “sees”, without extra turbulence.
- On top/side‑discharge transitions: pick the first straight section before the first bend/branch, ideally 1–2 duct diameters downstream of the outlet.
Step‑by‑step
- Drill the hole: Use the 6 mm bit at the location above. Lightly deburr the edges.
- Insert the tube: Push the manometer tube through so the tip sits flush with the inner wall (don’t poke it far into the airflow). Seal around the tube with a grommet or tape so air can’t leak.
- Power ON and run High Fan: Set the cooler to fan HIGH (ventilation is fine). Make sure the weather seal opens fully. Wait 2–3 minutes for airflow to settle.
- Read the pressure: Note the Pa value on the manometer.
- Around 80 Pa → Good for domestic systems.
- >100 Pa → Restriction likely (undersized/squashed duct, tight bends, too few/closed outlets, damper not opening).
- <50 Pa → Too much outlet area or negative pressure in the house (strong extraction fans, closed windows/doors).
- Finish up: Turn power OFF, remove the tube, and seal the hole with a blanking grommet (preferred) or aluminum tape.
Quick tips for a clean reading
- Keep the tube tip flush and perpendicular to the airflow—this avoids picking up velocity pressure.
- Don’t measure right next to elbows, take‑offs, dampers, or mesh.
- Check all outlets are open and the home has a relief path (windows/doors cracked open) so the cooler isn’t fighting negative pressure.
- If the reading hunts up and down, take a short 5–10 second average (many digital manometers have a damping setting).