Braemar MCMX VRF — Refrigerant Reclaim / Vacuum (Pump‑Down) Mode
Applies to:
Braemar MCMX VRF multi‑split outdoor units
(MCMX080D104 / 100D105 / 120D107 / 140D108 / 160D109)
Purpose
This article explains the approved methods technicians can use to place the system into a condition where refrigerant can be safely recovered (reclaimed) from a Braemar MCMX VRF system.
It also clarifies the difference between:
- A2 – Refrigerant Recovery Operation
- A8 – Aftersales Vacuum Mode
to ensure the correct function is used.
⚠️ Safety & Compliance
- Only qualified, licensed refrigeration technicians may perform refrigerant recovery
- Australian Greenhouse Office regulations apply
- Do not vent refrigerant to atmosphere under any circumstances
- Use approved recovery unit and cylinders
- Isolate mains power before disconnecting hoses or opening the system
- Follow PPE and site safety requirements
✅ Function Overview — A2 vs A8 (Critical for Correct Use)
| Function | Function Name | System Behaviour | Intended Use |
|---|---|---|---|
| A2 | Refrigerant Recovery Operation | System controls valves and runs compressor to move refrigerant toward outdoor unit | Maintenance use when system is operational |
| A8 | Aftersales Vacuum Mode | Opens all electronic expansion valves (EXVs) and system valves | Used to allow full system reclaim using external recovery unit |
✅ Important Clarification
- A2 does NOT open all valves — it is a controlled system recovery process
- A8 DOES open all valves — this is required to reclaim the entire system
➡ If the compressor is faulty or system cannot run:
A8 must be used
Overview of Options
There are two approved methods to place the system into a condition for refrigerant recovery:
Option 1 — Operational Pump‑Down via Cooling Run
Use only when:
- System is operational
- Compressor runs normally
Steps:
- Command all indoor units to Cooling at lowest set temperature
- Allow system to reach steady operation
- Turn OFF power at outdoor isolator
- Reclaim refrigerant using recovery unit
Result:
- Valves remain open from operation
- Enables full system recovery
⚠️ Use only when system operates without fault
Option 2 — Outdoor PCB Function A8: Vacuum / Pump‑Down Mode
Use when:
- Compressor is faulty
- System cannot run
- Full recovery is required
✅ Function Behaviour (Important)
When A8 is activated:
- All EXVs open
- System valves open across pipework and IDUs
- System becomes fully accessible for recovery
➡ This allows complete refrigerant reclaim using external equipment
A) 4‑Button MCMX Outdoor PCB
- Ensure system is in Standby (power ON, unit OFF)
- Press and hold SW1 for ~5 seconds (enter Function Settings)
- Use SW1 / SW2 to scroll to A8
- Press SW3 (OK)
- Select 01 — Vacuum / Pump‑Down Mode
- Press SW3 to confirm
➡ All valves open for recovery
- Turn power OFF at isolator
- Perform reclaim
B) 7‑Button MCMX Outdoor PCB (older models)
- Ensure system is in Standby
- Press SW3 (Function)
- Scroll to A8
- Press SW7 (OK)
➡ All valves open
- Turn power OFF
- Perform reclaim
After Recovery
- Restore power
- System returns to Off / Standby
Notes & Supporting Manual References
- Function Settings (A‑codes): Pages 28–31
- Service Modes (including recovery & vacuum): Pages 24–27
- Removal & Disposal: Pages 36–37
✅ Technician Checklist (Quick Reference)
- ✔ Confirm licensed technician and equipment
- ✔ Identify correct method:
- System operational → Option 1
- System faulty → A8
- ✔ Confirm PCB type (4‑button / 7‑button)
- ✔ If using A8 → confirm function is activated and confirmed
- ✔ Turn power OFF before recovery
- ✔ Recover full charge into approved cylinder
- ✔ Repair / leak test
- ✔ Evacuate system (≥ 100 µPa per install guidance)
- ✔ Restore power and confirm standby
?️ Troubleshooting
Cannot enter function mode
- Ensure:
- Unit powered ON
- In Off / Standby
- Debugging / preheat complete (if recent install or PCB replacement)
EXVs not opening / recovery slow
- Confirm:
- A8 selected and confirmed (not just displayed)
- Check:
- Communication faults
- PCB or system errors
Recovery incomplete
- A2 used instead of A8
- A8 not confirmed correctly
- System not fully opened
? Related References
- Outdoor PCB Function Map (A‑codes): Pages 28–31
- Debugging & Addressing: Pages 20–23
- Refrigerant charging data: Pages 18–19
⚡ Quick Guide — Field Use
✅ If system works normally
Cooling mode → Stabilise → Power OFF → Reclaim
✅ If system is faulty (correct method)
Enter A8 → Confirm → Power OFF → Reclaim
✅ PCB Shortcuts
4‑Button
Hold SW1 → A8 → OK → 01 → OK → Power OFF → Reclaim
7‑Button
SW3 → A8 → SW7 → Power OFF → Reclaim
✅ Key Takeaway
A2 = system moves refrigerant (compressor required)
A8 = system fully opens for reclaim (no compressor required)
Quick Guide
- If system works normally: Turn all indoor units ON in cooling at lowest temp → wait until running → switch OFF power at outdoor isolator → reclaim refrigerant.
- If using PCB mode:
- 4‑Button PCB: Power ON, unit OFF → hold SW1 for 5 sec → scroll to A8 → press SW3 → select 01 → press SW3 → turn power OFF → reclaim.
- 7‑Button PCB: Power ON, unit OFF → press SW3 → scroll to A8 → press SW7 → turn power OFF → reclaim.