SCHV / SDHV Ducted – P7 Fault (Quick Diagnostic Guide)
Applies to:
Braemar SCHV (Outdoor) + SDHV (Indoor) Ducted Reverse‑Cycle Systems
Where displayed: XE71, XK60, XK75 controllers or outdoor PCB fault indication.
What P7 Means
P7 = Outdoor unit is overheating, or the system thinks it’s overheating.
This protection is built into the inverter to prevent compressor or driver/module damage.
- Overheating commonly comes from blocked condenser coils, poor outdoor airflow, or weak outdoor fan performance.
- It can also be triggered by a faulty temperature sensor, incorrect sensor reading, or an overheating power/driver module.
- The Braemar service guide places P‑series errors under ducted split diagnostics in Error Codes for Ducted Split Systems (Section 35).
1. Quick Checks (Fix 90% of P7 Faults)
A. Outdoor Unit Airflow & Coil Condition
- Check the condenser coil for dirt, fluff, leaves or grass.
- A dirty coil dramatically increases discharge temperature.
- Ensure the outdoor fan spins strongly and ramps up properly.
- Wrong speed or weak airflow leads to overheating.
- Confirm the outdoor unit has clear air around it.
- No hot‑air recirculation, blocked fences, or stacked items behind it.
B. Temperature Sensor Checks
- Locate the temperature probe clipped onto the discharge pipe.
- Make sure it is firmly attached, insulation intact, and wiring is not damaged.
- A loose or faulty sensor can create false high readings.
- Sensor resistance can be confirmed using the Resistance Table (Section 36) in the service guide.
C. Refrigerant Condition (Simple Field Indicators)
Without gauges, look for:
- Frosting or hissing on pipework
- Very hot discharge pipe temperature
- Short cycling or hard compressor starts
These are indicators of possible under‑charge or restriction, which increases discharge temperature and triggers P7.
D. Electronics Overheating (Driver/IPM Module)
If coils and airflow are fine:
- Check outdoor PCB for darkened components, burn marks, or insect contamination.
- Poor airflow across the PCB can cause driver/IPM overheating, which is known on inverter platforms to activate P‑series protections.
2. Quick Step‑by‑Step Troubleshooting
Step 1 — Start with the Outdoor Unit
- Clean coil thoroughly
- Confirm fan operation & strong airflow
- Ensure outdoor unit is not boxed‑in
If issue persists → Step 2
Step 2 — Check the Sensor
- Ensure discharge sensor is clipped firmly
- Check wiring back to PCB
- Replace if visibly damaged
If issue persists → Step 3
Step 3 — Look for Refrigerant Symptoms
- Frosting, very hot discharge line, strange compressor sounds
- If suspicious → perform full pressure/temperature test
If issue persists → Step 4
Step 4 — Inspect Electronics
- Remove outdoor cover
- Check PCB for signs of overheating or damage
- Confirm airflow over PCB (some models cool the board through the condenser fan stream)
3. When to Escalate
Perform a full system diagnosis if:
- P7 returns immediately after cleaning coil and confirming strong airflow
- Sensor tests correctly using the Resistance Table (Section 36)
- Outdoor location has adequate ventilation
- No signs of refrigerant issues are present
At this point, suspect:
- Driver/IPM thermal fault
- Outdoor main PCB failure
4. Summary for Technicians
P7 = Outdoor unit too hot OR sensor reading that it’s too hot.
Fix order:
1) Coil & airflow → 2) Sensor → 3) Refrigerant → 4) PCB/Driver module
This ordering solves most P7 faults efficiently and avoids unnecessary component replacement.