Braemar (Historic) Legacy‑to‑Current Commercial Evaporative Coolers — Cross‑Reference (2026 Edition, Australia)

Current range launched in 2026 and manufactured in Lonsdale, South Australia; legacy historic units were manufactured in Albury, New South Wales (per internal program history).


Important Disclaimer — Read Before Use

This document is provided as a selection guide only. While all reasonable care has been taken to compile and verify information from current and legacy technical sources, final responsibility for product selection, installation quality, compliance, and performance rests with the installing company.


Before ordering or installing any product, you must cross‑check all model selections, electrical requirements, airflow/pressure data, dimensions, accessories, discharge configurations, and installation arrangements against the latest official Braemar installation manuals and technical data sheets for the specific model being selected and used. 


Product specifications, airflow ratings, accessories, and availability may change without notice. Seeley International does not accept liability for any loss, damage, incorrect operation, or non‑performance arising from selections or installations based solely on this guide.


What this page is for

Use this guide to replace older Braemar (and related) evaporative coolers with the current 2026 range (EA, RPSI, RPS, RPM, RPL, RPXL). It shows the closest modern model by airflow (free air, 0 Pa), high‑static alternatives (RPXL @ 80 Pa), plus electrical and dropper/outlet checks.


Configuration legend

  • D = Down Discharge (vertical outlet, direct to dropper/duct).
  • S = Side Discharge (horizontal outlet; supplied with flexible/canvas connector where specified).
  • T = Top Discharge (horizontal outlet; supplied with flexible/canvas connector where specified).
  • C = Chillcel® pads (honeycomb media used in the current commercial range; “Black Opal® Mini‑Cell Chillcel®” 

How to read the mappings

  • Primary = nearest equal‑or‑higher airflow at 0 Pa from EA/RPSI/RPS/RPM/RPL (best like‑for‑like starting point).
  • Alt = closest overall (small step down/up) if that better suit duct/motor constraints.
  • High‑static = RPXL option (airflow @ 80 Pa) where the system runs with real static pressure; RPXL fan curves to 400 Pa are provided.
  • Orientation: keep D/S/T the same to minimise duct changes (S/T commonly supplied with canvas/flexible connectors).

RPXL or RPL — quick rule of thumb

  • If the replacement will run mostly free‑air (short/low‑loss discharge), start at RPL (10 k / 12 k / 14 k published at 0 Pa).
  • If you expect meaningful duct static (long runs, branches, filters), use RPXL first. RPXL airflows are published at 80 Pa, with curves from 80 → 400 Pa so you can read delivered L/s at your estimated pressure.

A) Legacy EA / RPC (small–medium) → Current

Legacy modelLegacy airflow (l/s)Recommended current model(s)
RPC2501900Primary: EA120S (≈ 1980 l/s)
EA901900Primary: EA120S (≈ 1980 l/s)
RPC3202600Primary: RPSI2800DC (≈ 2740 l/s)
EA1202600Primary: RPSI2800DC (≈ 2740 l/s)
RPC4003280Primary: RPS3200DC (≈ 3520 l/s); Alt: RPS3200TC (≈ 3520 l/s)
EA1503280Primary: RPS3200DC (≈ 3520 l/s); Alt: RPS3200TC (≈ 3520 l/s)
RPC4503400Primary: RPS3200DC (≈ 3520 l/s); Alt: RPS3200TC (≈ 3520 l/s)

Plain‑English legacy note (EA/RPC):
RPC200/250/320/400/450 were produced 1997–2019 (metal RPC line). Spare Parts are limited or obsolete with no replacements; use the table above to jump to the closest modern EA or RPSI/RPS model. 


B) Legacy RPA (historic) → Current

Legacy modelLegacy airflow (l/s)Recommended current model(s)
RPA4004100Primary: RPM5000 (≈ 4960 l/s); Alt: RPS4000 (≈ 4060 l/s)
RPA4504420Primary: RPM5000 (≈ 4960 l/s); Alt: RPS4000 (≈ 4060 l/s)
RPA5004760Primary: RPM5000 (≈ 4960 l/s)
RPA6005860Primary: RPM6000 (≈ 6290 l/s)
RPA7007020Primary: RPM8000 (≈ 7940 l/s)
RPA9008810Primary: RPL10000 (≈ 10,650 l/s)
RPA10009890Primary: RPL10000 (≈ 10,650 l/s)
RPA120011,470Primary: RPL12000 (≈ 12,530 l/s)
RPA130012,750Primary: RPL14000 (≈ 13,330–14,260 l/s by orientation)
RPA140014,080Primary: RPL14000 (≈ 14,260 l/s); High‑static: RPXL16000 (≈ 17,300 @ 80 Pa)**
RPA150015,050Primary (closest): RPL14000 (≈ 14,260 l/s); High‑static: RPXL16000 (≈ 17,300 @ 80 Pa)**
RPA180017,500Primary (closest): RPL14000 (≈ 14,260 l/s); High‑static: RPXL16000 (≈ 17,300 @ 80 Pa)**
Legacy Note (RPA historic):
  • RPA400 (pre‑OR, historic production) was originally supplied as a single‑phase (1~) belt‑drive unit.
  • With the RPA‑OR (Optimised Range) refresh, RPA400 changed to a 3‑phase (3~) configuration.
  • A new single‑phase option for that airflow category was introduced as RPA320‑OR, replacing the original single‑phase RPA400 duty point (see Section C).
Practical changeover tip:
  • Replacing a historic single‑phase RPA400 and only 1‑phase supply is available? Prefer RPS3200 (1~) or RPSI2800 (ECM, 1~) depending on the required duty and duct static.
  • Where 3‑phase is available, changing to RPS4000 / RPM5000 remain valid.
General Legacy Note (RPA historic):
  • RPA400/450/500: 1996–2024. Spare parts are limited or obsolete with no replacements.
  • RPA600/700/900: 1996–2010. Spare parts are limited or obsolete with no replacements.
  • RPA1000: 2000–2010; RPA1200/1300/1400/1500: 2000–2007; RPA1800: 2005–2007. Parts are limited or obsolete with no replacements.
  • If the system has real duct static, the RPXL alternative is safer because performance is specified under pressure (80–400 Pa).

Earlier RPA400 units were single‑phase; in the later RPA‑OR refresh the RPA400 changed to 3‑phase, with RPA320‑OR introduced as the single‑phase successor. 


C) Legacy RPA‑OR (Optimised Range) → Current

Legacy modelLegacy airflow (l/s)Recommended current model(s)
RPA320‑OR3013Primary: RPS3200 (≈ 3520 l/s); Alt: RPSI2800 (≈ 2740 l/s)
RPA400‑OR3782Primary: RPS4000 (≈ 4060 l/s); Alt: RPS3200 (≈ 3520 l/s)
RPA450‑OR4596Primary: RPM5000 (≈ 4960 l/s)
RPA500‑OR4552Primary: RPM5000 (≈ 4960 l/s)

Legacy note (RPA‑OR):
Produced 2023–2025 as refreshed RPA sizes ahead of the 2026 launch of current range.


D) Legacy RPCQi‑OR → Current (small commercial ECM)

Legacy modelLegacy airflow @ 0 Pa (l/s)Recommended current model(s)
RPCQi‑OR 752400Primary: RPSI2500 (≈ 2400 l/s); Alt: RPSI2800 (≈ 2740 l/s)
RPCQi‑OR 1502740Primary: RPSI2800 (≈ 2740 l/s)


Legacy note (RPCQi‑OR / RPCQi):

  • RPCQi‑OR 75/150: 2023–2025 (Optimised Range).
  • RPCQi 75/150: 2019–2023 (first‑gen ECM).

E) Legacy EAQ → Current

Legacy modelLegacy airflowRecommended current model(s)
EAQ120SV (Side)≈ 2010 l/s @ 0 Pa (1720 @ 80 Pa)Primary: EA120S (≈ 1980 l/s); Alt: EA120S (≈ 1980 l/s) or RPSI2500 (≈ 2400 l/s) for ECM step‑up

(EAQ is a legacy polymer unit; use the EA120/RPSI selections above based on required duty and available static head.)


F) Legacy RPA4 → RPA30 (historic belt‑drive) → Current

Legacy modelLegacy airflow (l/s)Recommended current model(s)
RPA41730Primary: EA120D/T (≈ 2270 l/s); Alt: EA120S (≈ 1980 l/s)
RPA52420Primary: RPSI2800 (≈ 2740 l/s); Alt: RPSI2500 (≈ 2400 l/s)
RPA62920Primary: RPS3200 (≈ 3520 l/s)
RPA83455Primary: RPS3200 (≈ 3520 l/s)
RPA94420Primary: RPM5000 (≈ 4960 l/s); Alt: RPS4000 (≈ 4060 l/s)
RPA104760Primary: RPM5000 (≈ 4960 l/s)
RPA125860Primary: RPM6000 (≈ 6290 l/s)
RPA167020Primary: RPM8000 (≈ 7940 l/s)
RPA198810Primary: RPL10000 (≈ 10,650 l/s)
RPA2512,040Primary: RPL14000 (≈ 14,260 l/s); High‑static: RPXL16000 (≈ 17,300 @ 80 Pa)**
RPA3014,200Primary: RPL14000 (≈ 14,260 l/s); High‑static: RPXL16000 (≈ 17,300 @ 80 Pa)**

Legacy note (very early RPA):

  • RPA4/5/6/8 and RPA9/10/12/16/19: 1990–1996 (Pre-Seeley International Manufacture). Very early belt‑drives—normally replaced due to age and duct changes rather than airflow alone. Spare Parts are limited or obsolete with no replacements.

G) Legacy RPB (industrial legacy) → Current

Legacy modelLegacy airflow (l/s)Recommended current model(s)
RPB6005860Primary: RPM6000 (≈ 6290 l/s)
RPB7007200Primary: RPM8000 (≈ 7940 l/s)
RPB9008810Primary: RPL10000 (≈ 10,650 l/s)
RPB10009890Primary: RPL10000 (≈ 10,650 l/s)
RPB120011,470Primary: RPL12000 (≈ 12,530 l/s)
RPB130012,750Primary: RPL14000 (≈ 13,330–14,260 l/s)
RPB140014,080Primary: RPL14000 (≈ 14,260 l/s); High‑static: RPXL16000 (≈ 17,300 @ 80 Pa)**
RPB150015,050Primary (closest): RPL14000 (≈ 14,260 l/s); High‑static: RPXL16000 (≈ 17,300 @ 80 Pa)**
RPB1800 (D/T)17,690Primary (closest): RPL14000; High‑static: RPXL16000 (≈ 17,300 @ 80 Pa)**
RPB1800 (S)16,300Primary (closest): RPL14000; High‑static: RPXL16000 (≈ 17,300 @ 80 Pa)**

Legacy note (RPB):
RPB600–RPB1800: 2006–2025. Big industrial units that typically move to RPL (free‑air) or RPXL (high‑static) in changeovers.


Current Series — Electrical & Dropper / Outlet Sizes (for changeover)

Quick references for supply/protection and outlet continuity during quoting.

  • EA (EA120 reference)230 V / 1~ / 50 Hz; total power ≈ 1.135 kW max. Down: 550×550 mm, Top: 580×460 mm, Side: 506×385 mm.
  • RPSI (2500/2800)240 V / 1~ / 50 Hz; ~6 A / 1.3 kW (2500), ~9 A / 1.9 kW (2800). Down: 550×550, Top/Side: 390×507 mm.
  • RPS (3200/4000)RPS3200: 230 V / 1~ / 8.1 A / 1.6 kW max; RPS4000: 415 V / 3~ / 5.9 A / 2.8 kW max. Outlet: 610×610 mm.
  • RPM (5000/6000/8000)415 V / 3~; 5000: 6.6 A / 3.7 kW, 6000: 6.6 A / 3.7 kW, 8000: 11.1 A / 6.5 kW. Outlet: 780×760 mm.
  • RPL (10k/12k/14k)415 V / 3~; 10k: 14.2 A / 8.7 kW, 12k: 22.1 A / 12.9 kW, 14k: 29.4 A / 17.5 kW. Outlet: 890×890 mm.

RPXL (High‑static baseline — 80 Pa, with fan curves to 400 Pa)

  • Electrical415 V / 3~ / 50 Hz, IP55 motor, 2‑speed belt drive.
    RPXL16000: 32 A, 17.5 kW max input, fan Ø 900 mm.
    RPXL18000: 34 A, 20.5 kW max input, fan Ø 900 mm.
  • Outlet/Dropper1090×1090 mm (D/S/T).
  • Plumbing — ½″ BSP inlet; 1½″ BSP drain; typical drain 15 L/min.

Delivered airflow at common static pressures (high speed):

Model80 Pa120 Pa160 Pa200 Pa240 Pa280 Pa320 Pa360 Pa400 Pa
RPXL1600017,30016,36015,32014,08012,77011,0107,250
RPXL1800018,13017,58016,97016,24015,27013,87011,7908,760
(L/s)

Indicative input power (kW) at those points is listed in the RPXL sheet—e.g., RPXL16000 ≈ 16.9 kW @ 80 Pa → ≈ 10.3 kW @ 240 Pa; RPXL18000 ≈ 19.9 kW @ 120 Pa → ≈ 16.7 kW @ 240 Pa.


Notes & Changeover Guidance

1) Free‑air vs static

  • EA/RPSI/RPS/RPM/RPL flows are 0 Pa free‑air references; delivered flow reduces with duct static. Use series fan curves (RPSI/RPS/RPM/RPL) to estimate in‑service flow.
  • RPXL is specified at 80 Pa and stays predictable up to 400 Pa; use the quick‑reference table above

2) Discharge orientation & duct transitions

  • Keep D/S/T like‑for‑like. RPSI, RPS, RPM, RPL, EA connector sizes are listed above.
  • RPXL outlets are larger (1090×1090 mm) than RPL (890×890), RPM (780×760), RPS (610×610)—plan a dropper replacement or a transition/expansion (≤ 15–20°) to minimise friction/noise.

3) Electrical checks

  • Examples: RPS3200 → 230 V/1~, RPS4000 → 415 V/3~; RPM/RPL/RPXL → 415 V/3~ with rising current/kW by size.
  • RPXL: confirm 32 A / 17.5 kW (16k) or 34 A / 20.5 kW (18k); refine with the kW vs Pa values in the RPXL sheet when static is high.


Current Models Summary Table (2026)

Model SeriesModelAirflow (L/s)Rating PointConfigurations Available
EA SeriesEA120D2,2700 PaD = Down
EA120S1,9800 PaS = Side
EA120T2,2700 PaT = Top
RPSI (ECM)RPSI2500 (D/S/T)2,4000 PaD / S / T
RPSI2800 (D/S/T)2,7400 PaD / S / T
RPS (Belt‑drive)RPS3200 (D/S/T)3,5200 PaD / S / T
RPS4000 (D/S/T)4,0600 PaD / S / T
RPM (Belt‑drive)RPM5000 (D/S/T)4,9600 PaD / S / T
RPM6000 (D/S/T)6,2900 PaD / S / T
RPM8000 (D/S/T)7,9400 PaD / S / T
RPL (Large Belt‑drive)RPL10000 (D/S/T)10,6500 PaD / S / T
RPL12000 (D/S/T)12,5300 PaD / S / T
RPL14000 (D/S/T)14,260 (Down/Top) / 13,330 (Side)0 PaD / S / T
RPXL (High‑Static Industrial)RPXL16000 (D/S/T)17,30080 PaD / S / T
RPXL18000 (D/S/T)18,130120 Pa / 80 Pa curve also available

Optional Accessories (current models) — with part numbers

Notes:
650890 (Switch‑plate Assy MagIQtouch) is for RPSI only; other ranges use a 2-speed switch‑plate supplied.
• RPSI uses the MagIQtouch® / MagIQcool® controller ecosystem. 

Accessory / KitCompatible seriesWhat it does (plain English)Part number
MagIQtouch® Wall ControllerRPSIMain wall controller; 20 m loom; can expand via Link Module for multiple coolers094298
MagIQtouch® RF KitRPSIWireless control where a cable is impractical118574
MagIQtouch® Wi‑Fi Smart KitRPSIPhone/app control (needs MagIQtouch® wall control)118352
Link Module (with enclosure)RPSIExpands MagIQtouch® to multiple coolers / longer runs094274
MagIQtouch® Air SensorRPSIRemote temperature sensing for better control094328
MagIQtouch® Fan‑Delay KitRPSIRuns fan after pump to dry pads and reduce odours116747
BMS Industrial Controller MS1RPSIBMS / industrial interface116808
BMS Master M1RPSIBMS master interface114750
MagIQcool® ThermostatRPSISimple thermostat control (single cooler)094687
40 m Controller Lead (with ferrite)RPSILonger MagIQtouch® run122663
Switch‑plate Controller (MagIQtouch® SwitchPlate assy)RPSI onlyBasic ON/OFF • Variable Speed • PUMP control for RPSI650890
Variable Water Manager KitRPSISalinity monitoring + smart draining for RPSI073392
Auto‑Drain / Water Manager KitRPS / RPM / RPL / RPXLPeriodic drain to control salinity (non‑RPSI ranges)077444
Auto‑Drain Kit (EA series)(discontinuing)EAEA drain kit; run out stock “discontinued soon”098579
Roof Stand (RPS)RPSAdjustable, modular site stand (series‑specific)134192
Roof Stand (RPM / RPL)RPM, RPLAdjustable site stand for larger frames134215
Roof Stand – RPXL (TEMP)RPXLInterim RPXL stand (while stocks last)275581
New RPXL Rail KitRPXLAdapts common RPA/RPB stand to RPXL TBA
Brace (included with stands)RPS / RPM / RPL / RPXLStructural brace supplied with stands860923

Sizing & conversions (quick help)

  • L/s → m³/h: × 3.6 • L/s → CFM: × 2.118.
  • Legacy rule of thumb: m³/h ≈ L × W × H × airchanges (~40) + 12 %.


IMPORTANT!!! Useful Links (click below links to view)


Evaporative Air Conditioning Product Range - Seeley International


Installation Maintenance and Operation Manuals: Seeley International Pty Ltd 


Technical Specifications: Seeley International Pty Ltd


Electrical Supply, Protection (D‑Curve) & Commissioning — Braemar RPS / RPM / RPL / RPXL: Seeley International Pty Ltd