Braemar KDHA R32 Ducted Inverter – Service Manual KDHA-03-A
53-page Pdf attached
1. Overview
2. Safety & Compliance (Mandatory Reading)
2.1 General Safety Warnings
- Unit contains flammable refrigerant R32 (A2L)
- Refrigerant may be odourless
- Risk of fire, explosion, electric shock, and injury if procedures are not followed
- Always read the Service Manual before service or commissioning
2.2 Personnel Requirements
- Refrigerant work must be completed by qualified, licensed technicians
- Additional R32 flammable refrigerant training is required
- Competency may need to be documented (local regulatory requirement)
2.3 Ignition & Ventilation Controls
- No naked flames, heaters, or sparking devices in service area
- Maintain adequate ventilation during diagnosis, repair, and charging
- Flame-based leak detection is strictly prohibited
3. Model Identification & Compatibility
3.1 Indoor / Outdoor Pairing
Outdoor Model | Indoor Model | Capacity (Cooling / Heating) |
KCHA070D1B | KDHA070D1S | 7.1 kW / 8.0 kW |
KCHA100D1B | KDHA100D1S | 10.0 kW / 12.0 kW |
KCHA125D1B | KDHA125D1S | 12.5 kW / 14.0 kW |
KCHA140D1B | KDHA140D1S | 14.0 kW / 16.0 kW |
KCHA160D1B | KDHA160D1S | 16.0 kW / 18.0 kW |
4. Refrigerant Charge & Room Size Requirements
4.1 Base Refrigerant Charge
- Factory pre-charged (R32)
- Chargeless pipe length: 15 m
4.2 Additional Refrigerant Charge
Outdoor Model | Additional Charge |
KCHA070D1B | 16 g/m |
KCHA100–125D1B | 25 g/m |
KCHA140–160D1B | 35 g/m |
4.3 Minimum Room Area (R32)
- Based on total system refrigerant charge
- Ducted systems assume 2.2 m minimum installation height
- Refer to charge-to-area tables when assessing compliance
5. Electrical Data & Wiring
5.1 Power Supply
- 230 V / 50 Hz / Single phase
- Acceptable range under load: 218.5 – 253 Vac
5.2 Outdoor Unit Protection
Model | Max Current | Min Breaker |
KCHA070D1B | 12.5 A | 20 A |
KCHA100D1B | 20.0 A | 32 A |
KCHA125D1B | 25.0 A | 32 A |
KCHA140D1B | 28.0 A | 40 A |
KCHA160D1B | 32.0 A | 40 A |
- All‑pole isolator (≥3 mm separation)
- Correct earth continuity
- Secure terminal connections
6. Leak Detection & Evacuation (R32)
6.1 Vacuum Procedure
- Connect manifold set to gas service port
- Evacuate system to ≤500 microns
- Isolate and hold for 15 minutes
- Pressure rise indicates a leak – recover, repair, and repeat
6.2 Permitted Leak Detection
- ✅ R32‑compatible electronic detector
- ✅ Bubble / dye method
- ❌ Flame‑based detection
7. Error Codes – KDHA Series (Service Articles)
Error Code | Protection / Fault Description | System Area | Primary Reference (KDHA‑03‑A) | Additional Reference |
qC | Primary control ↔ driver communication fault | Outdoor PCB / Inverter | p.28–30 | p.46 (detailed logic) |
PA | AC over‑current protection | Outdoor unit | p.28–30 | p.15 (electrical data & wiring) |
P0 | IPM / inverter module protection | Outdoor unit | p.28–30 | p.15 (electrical data & wiring) |
P1 | Supply voltage protection (over / under) | Outdoor unit | p.28–30 | p.15 (electrical data & wiring) |
P2 | Compressor over‑temperature protection | Compressor | p.28–30 | – |
P3 | Outdoor fan motor protection | Outdoor fan | p.28–30 | p.11–12 (outdoor clearances & airflow) |
P4 | Inverter drive protection | Inverter module | p.28–30 | – |
P6 | DC bus voltage protection | Inverter power circuit | p.28–30 | p.15 (electrical data & wiring) |
E1 | High pressure protection | Refrigerant system | p.28–30 | p.14 (refrigerant charge), p.27 (leak detection) |
E2 | Indoor coil freeze protection | Indoor unit | p.28–30 | – |
E3 | Low pressure protection | Refrigerant system | p.28–30 | p.14 (refrigerant charge), p.27 (leak detection) |
E4 | Compressor discharge temperature protection | Compressor | p.28–30 | p.14 (refrigerant charge) |
E5 | Outdoor temperature protection | Outdoor sensors | p.28–30 | p.11–12 (outdoor clearances & airflow) |
E6 | Indoor ↔ outdoor communication fault | IDU / ODU comms | p.28–30 | p.15–16 (wiring), p.18–19 (diagrams) |
Error Code: qC
- Communication wiring disconnected, damaged, or poor termination
- Primary control board fault
- Inspect and reseat communication cable between primary control and driver
- Check continuity of wiring
- Replace primary control board if wiring is confirmed okay
- Error Codes: p.28–30
- Detailed troubleshooting: p.46
Error Code: PA
- Outdoor fan or compressor abnormal current draw
- Supply voltage instability
- Main PCB fault
- Verify supply voltage under load
- Inspect compressor and fan motor for mechanical binding
- Check outdoor PCB
Error Code: P0
- Power module fault
- Voltage surge or phase imbalance
- Power reset and re-test
- Verify incoming supply stability
- Replace inverter module if fault reoccurs
Error Code: P1
- Overvoltage or undervoltage condition
- Measure supply voltage at outdoor unit under load
- Confirm breaker sizing and cable gauge
Error Code: E1
- Restricted condenser airflow
- Overcharge of refrigerant
- Outdoor fan fault
- Inspect outdoor airflow and clear obstructions
- Confirm fan operation
- Verify refrigerant charge against pipe length
Error Code: E2
- Low airflow
- Dirty filters or blocked ducts
- Low refrigerant charge
- Inspect filters and ductwork
- Verify airflow and ESP settings
- Leak check and confirm charge
Error Code: E6
- Communication wiring reversed or open circuit
- Earthing fault
- Verify terminal matching (N(1), 2, L(3))
- Check earth continuity
8. Common Troubleshooting Scenarios
Unit Inoperative
- Verify mains voltage under load
- Check breaker, isolator, and RCD
- Inspect indoor/outdoor communication cable
Poor Performance
- Confirm airflow and ESP selection
- Verify refrigerant charge distance correction
- Inspect filters and return air path
9. Servicing R32 Systems – Field Checklist
- ✅ Ventilated area
- ✅ No ignition sources
- ✅ R32‑rated recovery and detection equipment
- ✅ Fire extinguisher available
- ❌ Vent refrigerant
- ❌ Braze without nitrogen purge
- ❌ Reuse flares indoors
10. Removal & Disposal
- Isolate all electrical supplies
- Recover all refrigerant using approved recovery unit
- Dispose of oil and components per local regulations