Braemar KDHA R32 Ducted Inverter – Service Manual KDHA-03-A
⚠️ Safety Notice – Reverse Cycle Air Conditioners
This equipment must only be installed, commissioned, serviced and repaired by suitably qualified and licensed personnel.
Before commencing work, complete a task-specific risk assessment and ensure electrical isolation procedures, safe access, adequate service clearances and appropriate PPE have been considered. All work must comply with applicable regulations, standards and manufacturer requirements.
Particular care must be taken when working around electrical systems, refrigerant circuits, moving parts, roof spaces, ceiling spaces, confined spaces and working-at-heights hazards where applicable.
Do not proceed if safe access, required clearances, confined space risks or appropriate safety controls cannot be achieved and maintained.
Safety takes priority over diagnosis, repairs, installation schedules and customer expectations. If the task cannot be completed safely, it must not proceed until the risks have been adequately controlled.
Pdf attached
1. Overview
2. Safety & Compliance (Mandatory Reading)
2.1 General Safety Warnings
- Unit contains flammable refrigerant R32 (A2L)
- Refrigerant may be odourless
- Risk of fire, explosion, electric shock, and injury if procedures are not followed
- Always read the Service Manual before service or commissioning
2.2 Personnel Requirements
- Refrigerant work must be completed by qualified, licensed technicians
- Additional R32 flammable refrigerant training is required
- Competency may need to be documented (local regulatory requirement)
2.3 Ignition & Ventilation Controls
- No naked flames, heaters, or sparking devices in service area
- Maintain adequate ventilation during diagnosis, repair, and charging
- Flame-based leak detection is strictly prohibited
3. Model Identification & Compatibility
3.1 Indoor / Outdoor Pairing
Outdoor Model | Indoor Model | Capacity (Cooling / Heating) |
KCHA070D1B | KDHA070D1S | 7.1 kW / 8.0 kW |
KCHA100D1B | KDHA100D1S | 10.0 kW / 12.0 kW |
KCHA125D1B | KDHA125D1S | 12.5 kW / 14.0 kW |
KCHA140D1B | KDHA140D1S | 14.0 kW / 16.0 kW |
KCHA160D1B | KDHA160D1S | 16.0 kW / 18.0 kW |
4. Refrigerant Charge & Room Size Requirements
4.1 Base Refrigerant Charge
- Factory pre-charged (R32)
- Chargeless pipe length: 15 m
4.2 Additional Refrigerant Charge
Outdoor Model | Additional Charge |
KCHA070D1B | 16 g/m |
KCHA100–125D1B | 25 g/m |
KCHA140–160D1B | 35 g/m |
4.3 Minimum Room Area (R32)
- Based on total system refrigerant charge
- Ducted systems assume 2.2 m minimum installation height
- Refer to charge-to-area tables when assessing compliance
5. Electrical Data & Wiring
5.1 Power Supply
- 230 V / 50 Hz / Single phase
- Acceptable range under load: 218.5 – 253 Vac
5.2 Outdoor Unit Protection
Model | Max Current | Min Breaker |
KCHA070D1B | 12.5 A | 20 A |
KCHA100D1B | 20.0 A | 32 A |
KCHA125D1B | 25.0 A | 32 A |
KCHA140D1B | 28.0 A | 40 A |
KCHA160D1B | 32.0 A | 40 A |
- All‑pole isolator (≥3 mm separation)
- Correct earth continuity
- Secure terminal connections
6. Leak Detection & Evacuation (R32)
6.1 Vacuum Procedure
- Connect manifold set to gas service port
- Evacuate system to ≤500 microns
- Isolate and hold for 15 minutes
- Pressure rise indicates a leak – recover, repair, and repeat
6.2 Permitted Leak Detection
- ✅ R32‑compatible electronic detector
- ✅ Bubble / dye method
- ❌ Flame‑based detection
7. Error Codes – KDHA Series (Service Articles)
Error Code | Protection / Fault Description | System Area | Primary Reference (KDHA‑03‑A) | Additional Reference |
qC | Primary control ↔ driver communication fault | Outdoor PCB / Inverter | p.28–30 | p.46 (detailed logic) |
PA | AC over‑current protection | Outdoor unit | p.28–30 | p.15 (electrical data & wiring) |
P0 | IPM / inverter module protection | Outdoor unit | p.28–30 | p.15 (electrical data & wiring) |
P1 | Supply voltage protection (over / under) | Outdoor unit | p.28–30 | p.15 (electrical data & wiring) |
P2 | Compressor over‑temperature protection | Compressor | p.28–30 | – |
P3 | Outdoor fan motor protection | Outdoor fan | p.28–30 | p.11–12 (outdoor clearances & airflow) |
P4 | Inverter drive protection | Inverter module | p.28–30 | – |
P6 | DC bus voltage protection | Inverter power circuit | p.28–30 | p.15 (electrical data & wiring) |
E1 | High pressure protection | Refrigerant system | p.28–30 | p.14 (refrigerant charge), p.27 (leak detection) |
E2 | Indoor coil freeze protection | Indoor unit | p.28–30 | – |
E3 | Low pressure protection | Refrigerant system | p.28–30 | p.14 (refrigerant charge), p.27 (leak detection) |
E4 | Compressor discharge temperature protection | Compressor | p.28–30 | p.14 (refrigerant charge) |
E5 | Outdoor temperature protection | Outdoor sensors | p.28–30 | p.11–12 (outdoor clearances & airflow) |
E6 | Indoor ↔ outdoor communication fault | IDU / ODU comms | p.28–30 | p.15–16 (wiring), p.18–19 (diagrams) |
Error Code: qC
- Communication wiring disconnected, damaged, or poor termination
- Primary control board fault
- Inspect and reseat communication cable between primary control and driver
- Check continuity of wiring
- Replace primary control board if wiring is confirmed okay
- Error Codes: p.28–30
- Detailed troubleshooting: p.46
Error Code: PA
- Outdoor fan or compressor abnormal current draw
- Supply voltage instability
- Main PCB fault
- Verify supply voltage under load
- Inspect compressor and fan motor for mechanical binding
- Check outdoor PCB
Error Code: P0
- Power module fault
- Voltage surge or phase imbalance
- Power reset and re-test
- Verify incoming supply stability
- Replace inverter module if fault reoccurs
Error Code: P1
- Overvoltage or undervoltage condition
- Measure supply voltage at outdoor unit under load
- Confirm breaker sizing and cable gauge
Error Code: E1
- Restricted condenser airflow
- Overcharge of refrigerant
- Outdoor fan fault
- Inspect outdoor airflow and clear obstructions
- Confirm fan operation
- Verify refrigerant charge against pipe length
Error Code: E2
- Low airflow
- Dirty filters or blocked ducts
- Low refrigerant charge
- Inspect filters and ductwork
- Verify airflow and ESP settings
- Leak check and confirm charge
Error Code: E6
- Communication wiring reversed or open circuit
- Earthing fault
- Verify terminal matching (N(1), 2, L(3))
- Check earth continuity
8. Common Troubleshooting Scenarios
Unit Inoperative
- Verify mains voltage under load
- Check breaker, isolator, and RCD
- Inspect indoor/outdoor communication cable
Poor Performance
- Confirm airflow and ESP selection
- Verify refrigerant charge distance correction
- Inspect filters and return air path
9. Servicing R32 Systems – Field Checklist
- ✅ Ventilated area
- ✅ No ignition sources
- ✅ R32‑rated recovery and detection equipment
- ✅ Fire extinguisher available
- ❌ Vent refrigerant
- ❌ Braze without nitrogen purge
- ❌ Reuse flares indoors
10. Removal & Disposal
- Isolate all electrical supplies
- Recover all refrigerant using approved recovery unit
- Dispose of oil and components per local regulations