CE52 Central Controller – Connection Wiring for Single Outdoor Unit (VRF / MCHX)
Pdf Owner's Manual CE52-24F(C)-B AU1906 attached for reference
CE52-24/F9(C) - Central Controller
Purpose
This article explains how to correctly connect a CE52 Central Controller when a VRF system has ONE Outdoor Unit (ODU).
It also explains:
- What the D1 / D2 daisy chain is
- How the CE52 interacts with it
- Why two wiring options are allowed for single‑ODU systems only
What Is the D1 / D2 Daisy Chain?
- D1 and D2 are the communication terminals used to link Indoor Units (IDUs) together
- Indoor units are wired IDU → IDU → IDU in a straight line (daisy chain)
- The chain has:
- A first indoor unit
- A last indoor unit
- The last indoor unit is where controllers or termination resistors are connected
✅ This D1/D2 chain exists on all VRF systems, regardless of how many outdoor units are fitted.
⚠️ Important:
- Star or radial wiring is NOT permitted
- Communication wiring must not run from the outdoor unit to each indoor unit individually
- The D1/D2 network must always be installed in series (daisy‑chain only)
Single Outdoor Unit
✅ When there is ONE Outdoor Unit, the CE52 can be connected in either of the following ways:
- Via the Indoor Unit D1 / D2 daisy chain
- Directly to the Outdoor Unit G1 / G2 terminals
✅ Both options are valid ONLY when there is a single ODU
Option 1 (Most Common) – CE52 Connected to the D1 / D2 Daisy Chain
What this means:
- Indoor units are already linked together via D1/D2
- The CE52 connects to D1 and D2 on the LAST indoor unit
In simple terms:
The CE52 joins the same communication wiring that all indoor units are using.
Important points:
- The CE52 does NOT connect in the middle of the chain
- It always connects at the end
- A matching (120-ohm termination) resistor must be connected to G1 / G2 at the CE52
✅ This is the most common and simplest method
⚠️ Critical wiring rules:
- Only ONE termination resistor is permitted on the communication network
- The resistor supplied in the outdoor unit pack‑out kit must be used
Option 2 – CE52 Connected Directly to the Outdoor Unit (G1 / G2)
What this means:
- The CE52 does not connect to the D1/D2 wiring
- It connects directly to G1 / G2 on the Outdoor Unit
⚠️ Critical clarification about D1 / D2:
- Even though the CE52 is connected to G1/G2, the indoor D1/D2 daisy chain still exists
- Indoor units MUST still be wired IDU → IDU in series
- Star configurations remain prohibited
✅ When using this method:
- The termination resistor must be installed on D1 / D2 of the LAST indoor unit
✅ This option is ONLY allowed when there is ONE ODU

Why Both Options Work (Single ODU)
With only one outdoor unit:
- The indoor (D1/D2) and outdoor (G1/G2) networks are treated as one system
- The CE52 can communicate from either end
Common Single‑ODU Mistakes
❌ CE52 connected mid‑way along D1/D2
❌ Star or radial communication wiring
❌ No termination resistor fitted
❌ Termination resistor fitted at multiple locations
❌ Communication cable screen not earthed correctly
CE52 Central Controller Connections
Additional Terminal Functions
F1 / F2
- Used for Fire Trip shutdown input
- Typically connected to:
- Fire Control Panels
- Commercial / industrial fire systems
Power Supply & Wiring
Installation and wiring must be done by a qualified electrician.
Power Requirements
- Uses standard household power (240 V AC)
- Works with 50 or 60 Hz
- Only use an approved 3‑wire power cable
- Cable size: 1.5 mm²
- Must meet electrical safety standards
Connecting the Wires
- Connect the communication wires to terminals G1 and G2
- Option 1 only: Fit the supplied 120 -ohm resistor across G1 and G2
- Connect Neutral to N
- Connect Live to L
- Connect Earth to the earth terminal on the metal box cover
✅ Ensure all screws and terminals are tight before power‑up

Termination Resistor – Mandatory Requirement
Resistor must be connected to G1 / G2 (Option 1)
⚠️ IMPORTANT – Option 2:
- Fit the 120-ohm termination resistor across D1 / D2 of the LAST indoor unit
✅ Every communication network gets:
- ONE termination resistor
- Fitted ONLY at the far end
- Never more than one
✅ The “far end” depends on where the CE52 is connected
Communication Cable Screen (Earth) – Critical
- Use shielded, twisted‑pair communication cable
- The cable screen (drain wire) must be:
- Earthed at ONE point only (typically at the outdoor unit)
- Do NOT earth the screen at multiple locations
⚠️ Incorrect screen earthing can cause:
- Communication dropouts
- Random indoor unit faults
- CE52 offline alarms

