Pdf Owner's Manual CE52-24F(C)-B AU1906 attached for reference
CE52-24/F9(C) - Central Controller
Overview
This article provides wiring requirements, termination rules, and common fault causes for installations where a CE52 Central Controller is connected to multiple outdoor VRF/MCHX units. Incorrect termination, wiring topology, or addressing will result in communication faults or system instability.
Power Supply Requirements
⚠️ Important
- The CE52 Central Controller requires a separate power supply.
- Power must be connected to L / N / E terminals on the controller.
- The CE52 is not powered via the communication network.
Communication Wiring – Multiple Outdoor Solution
D1 / D2 Indoor Communication Network
- Indoor units must be connected in series (daisy chain) on the D1/D2 communication line.
- Star wiring configurations are NOT permitted and will cause communication errors.
✅ Termination Requirement
- The final indoor unit on the D1/D2 chain must have a 120 Ω termination resistor.
- The termination resistor is supplied in the outdoor unit pack‑out kit.
G1 / G2 Central Controller Network
- The CE52 Central Controller is supplied with a 120 Ω termination resistor.
- This resistor must be fitted across the G1/G2 terminals on the Central Controller.
Do NOT fit termination resistors to the G1/G2 outdoor network
Correct Rule:
120 Ω termination is only required at the Central Controller (G1/G2), not at outdoor units.
Common Installation Errors & Communication Fault Causes
| Issue | Description |
|---|---|
| Incorrect termination location | 120 Ω termination resistor not fitted to G1/G2 on the Central Controller |
| Star wiring topology | Communication wiring installed from outdoor to each indoor unit instead of daisy‑chain |
| Outdoor addressing fault | Outdoor unit DIP switch settings not sequential on a Multiple Outdoor installation |
| Shield not earthed | Communication cable earth screen/drain wire not terminated correctly to earth |
| Incorrect resistor placement | Termination resistor fitted to outdoor units instead of the controller |
Correct Rule (Check)
One termination resistor only, fitted at the correct end of each network
- D1/D2 → Final indoor unit only
- G1/G2 → CE52 Central Controller only
- Never terminate outdoor G1/G2 terminals
Outdoor Unit Addressing (Multiple Outdoor Installations)
- All outdoor units must be addressed sequentially using the DIP switches.
- Duplicate or skipped addressing will prevent the CE52 from correctly identifying connected units.
✅ Always confirm:
- Address order
- DIP switch positions
- Match against commissioning documentation
Communication Cable Shielding
- Use screened communication cable for all D1/D2 and G1/G2 networks.
- The earth screen/drain wire must be bonded to earth correctly.
- Floating or incorrectly bonded shields may introduce noise and intermittent faults.
Key Takeaways
- CE52 requires independent power supply
- Daisy chain only – no star wiring
- 120 Ω termination required at:
- Final indoor unit (D1/D2)
- Central Controller ONLY (G1/G2)
- Outdoor units on G1/G2 must never be terminated
- Confirm outdoor DIP switch sequencing
- Earth communication cable shielding correctly
CE52 Central Controller Connections

Additional Terminal Functions
F1 / F2
- Used for Fire Trip shutdown input
- Typically connected to:
- Fire Control Panels
- Commercial / industrial fire systems
Power Supply & Wiring
Installation and wiring must be done by a qualified electrician.
Power Requirements
- Uses standard household power (240 V AC)
- Works with 50 or 60 Hz
- Only use an approved 3‑wire power cable
- Cable size: 1.5 mm²
- Must meet electrical safety standards
Connecting the Wires
- Connect the communication wires to terminals G1 and G2
- Connect the Neutral wire to the terminal marked N.
- Connect the Live wire to the terminal marked L.
- Connect the earth (ground) wire to the earth terminal on the metal box cover.
✅ Make sure all screws and terminals are tight before turning the power on.

120-ohm Resister must be connected to G1, G2
Communication Cable Screen (Earth) – Critical
- Use shielded, twisted‑pair communication cable
- The cable screen (drain wire) must be:
- Earthed at ONE point only (typically at the outdoor unit)
- Do NOT earth the screen at multiple locations
⚠️ Incorrect screen earthing can cause:
- Communication dropouts
- Random indoor unit faults
- CE52 offline alarms
