Fault Code E6: Indoor / Outdoor Communication Fault - Braemar KDHA R32 Ducted Inverter (KDHA070–160 / KCHA070–160)
Applies To
Braemar KDHA R32 ducted inverter systems only, as covered in KDHA‑03‑A Service Manual.
Indoor Units
- KDHA070D1S
- KDHA100D1S
- KDHA125D1S
- KDHA140D1S
- KDHA160D1S
Outdoor Units
- KCHA070D1B
- KCHA100D1B
- KCHA125D1B
- KCHA140D1B
- KCHA160D1B
Service Manual Reference (KDHA‑03‑A)
- Error Code Listing: Error Codes section, pages 28–30 (E6 – Communication Fault)
- Diagnostic Guidance: Troubleshooting – Flowcharts, from page 31 onward (communication and control faults)
- Wiring Schematics (Indoor ↔ Outdoor): pages 16–19
What Does E6 Mean?
E6 indicates a communication fault between the indoor unit and the outdoor unit.
If valid communication signals are not detected between the indoor and outdoor control boards within a specified time, the system will stop operation as a protective measure.
Common Symptoms
- System does not start heating or cooling
- Indoor fan may run, but compressor does not operate
- E6 fault code displayed on the wired controller or indoor unit display
- Power reset may temporarily clear the fault, but E6 returns
Likely Causes
Based on the KDHA service manual error code logic and troubleshooting flowcharts, common causes include:
- Communication wiring issue
- Communication cable disconnected or not terminated correctly
- Damaged cable (cut, crushed, or pinched)
- Poor or corroded terminal connections
- Incorrect wiring
- Wiring connected to incorrect terminals
- Incorrect polarity between indoor and outdoor units
- Power supply issue
- Power not present at either indoor or outdoor unit
- Voltage instability affecting control boards
- Control board fault
- Indoor PCB fault
- Outdoor main PCB fault
Notes for Service
- Verify the indoor ↔ outdoor communication cable is connected to the correct terminals at both units and is secure.
- Inspect wiring for damage, corrosion, or loose connections.
- Confirm correct polarity and wiring size as per the KDHA wiring diagrams.
- Ensure stable and correct power supply to both indoor and outdoor units.
- If wiring and power checks are completed and E6 persists, follow the KDHA troubleshooting flowcharts to isolate indoor vs outdoor PCB faults. Braemar KDHA R32 Ducted Inverter – Service Manual KDHA-03-A: Seeley International Pty Ltd
- All service work must be carried out by licensed technicians trained in handling flammable refrigerant R32, in accordance with KDHA service manual safety requirements.